Combined Resistance Budget

DoD Manual 4145.26 limits the combined resistance of the person’s body, conductive shoes, and floor-to-ground path to 1,000,000 ohms (1 MΩ). The limit does not apply to the floor alone.

These provisions come from the DoD Contractor’s Safety Manual for Ammunition and Explosives, dated 13 March 2008 and incorporating Change 2 of 31 August 2018.

How the shared resistance limit works

Clause
C6.4.7.5.1
Combined max
1,000,000 ohms

Paragraph C6.4.7.5.1 permits different maximums for the floor-to-ground path and the person’s body plus shoes, provided their combined resistance does not exceed 1,000,000 ohms.

The manual gives this example:

Part of the grounding pathMaximum resistance in the example
Floor to the ground system500,000 ohms
Person’s body plus conductive shoes500,000 ohms
Combined path1,000,000 ohms

The equal split is an example, not a required allocation. The controlling requirement is the combined limit.

Minimum resistance still applies

Clause
C6.4.7.5.2

The allocation does not remove the separate minimum-resistance provision in C6.4.7.5.2. Floor-to-ground and tabletop-to-ground resistance must each:

  • Exceed 40,000 ohms in areas with 110-volt service.
  • Exceed 75,000 ohms in areas with 220-volt service.

A ground fault interrupt circuit also meets this minimum-resistance requirement.

The DoD conductive-floor guide puts these resistance requirements alongside the footwear checks, floor-testing schedule, and installation requirements.

Frequently asked questions

No. DoD Manual 4145.26 C6.4.7.5.1 gives that split as an example. Different maximums may be set for the floor-to-ground path and the person’s body plus conductive shoes, provided their combined resistance does not exceed 1,000,000 ohms.

No. DoD Manual 4145.26 C6.4.7.5.2 separately requires floor-to-ground and tabletop-to-ground resistance to exceed 40,000 ohms in areas with 110-volt service and 75,000 ohms in areas with 220-volt service. A ground fault interrupt circuit also meets this minimum-resistance requirement.

Blog

Craftsman Publishes 2026–2027 ESD Flooring Technical Guide
Craftsman’s 2026–2027 ESD flooring technical guide brings together more than 70 resources on installation, field testing, acceptance criteria and closeout documentation.
ESD Epoxy Flooring Case Study: 34,000 SF Dallas, TX
• Tier-1 electronics QA environment • 34,000 SF ESD epoxy flooring • Phased work in occupied space • Verification + closeout documentation
ESD Epoxy Flooring Case Study: 67,000 SF | Houston, TX
• Tier-1 electronics manufacturing / QA (ESD-controlled) • 67,000 SF ESD epoxy flooring • Product-cycle reconfiguration program • Phased install; moisture + resistance testing; closeout docs