Type C FIBC Grounding System Scope

A Type C flexible intermediate bulk container (FIBC) grounding system checks electrical contact between the bag’s interwoven conductive threads and its ground connection points, according to Newson Gale’s Grounding & Bonding Applications, Issue 4. It does not validate the bag’s general condition or verify electrical continuity between an inner liner and those threads.

Responsibility for bag suitability and condition

Source
Newson Gale guide
Responsible
Site owner

Newson Gale’s guide assigns responsibility for the suitability and general condition of a Type C bag to the site owner.

Evaluating an FIBC with a liner under TRGS 727

Rule
TRGS 727, §6.6(8)
Edition
Jan. 2016, corr. July 2016

TRGS 727, the German technical rule on preventing ignition hazards from electrostatic charges, addresses liner use separately. The January 2016 edition, corrected July 2016, requires evaluation of the packaging as a whole when liner bags are used, because the manufacturer’s type classification usually does not cover them.

This is one of the FIBC selection and grounding requirements in section 6.6(8). Annex C also notes that liner bags can change the behavior of a Type C FIBC.

Frequently Asked Questions

According to Newson Gale’s Grounding & Bonding Applications guide, Issue 4, it checks electrical contact between the bag’s interwoven conductive threads and its ground connection points. It does not validate general bag condition or verify continuity between an inner liner and those threads.

Newson Gale’s Grounding & Bonding Applications guide, Issue 4, assigns responsibility for the suitability and general condition of a Type C bag to the site owner.

TRGS 727 requires evaluation of the packaging as a whole because the manufacturer’s type classification usually does not cover liner bags. Annex C also notes that liners can change the behavior of a Type C FIBC.

Blog

Craftsman Publishes 2026–2027 ESD Flooring Technical Guide
Craftsman’s 2026–2027 ESD flooring technical guide brings together more than 70 resources on installation, field testing, acceptance criteria and closeout documentation.
ESD Epoxy Flooring Case Study: 34,000 SF Dallas, TX
• Tier-1 electronics QA environment • 34,000 SF ESD epoxy flooring • Phased work in occupied space • Verification + closeout documentation
ESD Epoxy Flooring Case Study: 67,000 SF | Houston, TX
• Tier-1 electronics manufacturing / QA (ESD-controlled) • 67,000 SF ESD epoxy flooring • Product-cycle reconfiguration program • Phased install; moisture + resistance testing; closeout docs