Floor Contact and Equipment Bonding

No. Floor contact alone does not meet the permanent-equipment bonding requirement in DoD Manual 4145.26. DA Pam 385-64 separately states that equipment is not considered grounded solely because it rests on a conductive floor or tabletop.

DoD Manual 4145.26: permanent-equipment bonding

Clause
C6.4.5
Edition
13 Mar 2008, Change 2

Paragraph C6.4.5 of DoD Manual 4145.26 states that permanent equipment in contact with a conductive floor or tabletop does not, by that contact, meet the bonding requirement to the ground system.

The source is the DoD Contractor’s Safety Manual for Ammunition and Explosives, dated 13 March 2008 and incorporating Change 2 of 31 August 2018. Its separate requirements for personnel grounding, footwear, and testing are covered in the DoD conductive-floor guide.

DA Pam 385-64: equipment grounding

Item
(c), general requirements
Edition
24 July 2023

DA Pam 385-64 states that equipment in contact with a conductive floor or tabletop is not considered grounded solely due to its position on that surface. This is item (c) of the general requirements for conductive floors, plates, mats, and runners.

The source is the Department of the Army pamphlet Ammunition and Explosives Safety Standards, dated 24 July 2023.

Frequently asked questions

No. Under DoD Manual 4145.26, paragraph C6.4.5 (13 March 2008, incorporating Change 2 of 31 August 2018), permanent equipment in contact with a conductive floor does not, by that contact, meet the bonding requirement to the ground system. The same provision covers contact with conductive tabletops.

No. DA Pam 385-64 (24 July 2023) states that equipment in contact with a conductive floor or tabletop will not be considered grounded solely due to its position on that surface.

Blog

Craftsman Publishes 2026–2027 ESD Flooring Technical Guide
Craftsman’s 2026–2027 ESD flooring technical guide brings together more than 70 resources on installation, field testing, acceptance criteria and closeout documentation.
ESD Epoxy Flooring Case Study: 34,000 SF Dallas, TX
• Tier-1 electronics QA environment • 34,000 SF ESD epoxy flooring • Phased work in occupied space • Verification + closeout documentation
ESD Epoxy Flooring Case Study: 67,000 SF | Houston, TX
• Tier-1 electronics manufacturing / QA (ESD-controlled) • 67,000 SF ESD epoxy flooring • Product-cycle reconfiguration program • Phased install; moisture + resistance testing; closeout docs